Specification
Device data | Description |
Article number | WCCLite |
Product Description | WCCLite – mini RTU and gateway |
Configuration software | WCC Excel utility, Putty, Web browser |
Warranty | 2 years |
General | WCCLite features |
Functionality | Freely scalable RTU with included all supported protocols and functions for utilities, grid and renewables automation solutions. |
RTU functionality | – Reading Process events from the input/output modules. – Send commands to the output modules. – Communication with sub-devices to collect events and execute commands. – Communicating with control systems and other IOT systems. – Handling the configuration via WEB Browser and Elseta configuration tools; – Monitor communication status with sub-devices. – Sequence-of-Event (SOE). – Execute user scripts to enable custom automation and regulation algorithms. – Connectivity: LAN/WAN, Mobile (4G LTE), VPN. – Firewall (rules-based). |
Data exchange | WCCLite can support up to 16 host systems including hot-standby SCADA systems. Every IEC 60870-5 protocol can have shared or independent buffers of events and support multiple SCADA communications at the same time. |
Data collection | WCCLite series supports the collection of data from up to 50 sub-devices, e.g. IEDs, meters, IO’s, and Inverters. Each sub-device connected to WCCLite is supervised and shown status on the diagnostic screen. |
PLC | WCCLite support: – distributed PLC-based IEC 61499 standard; – Script execution engine (recommended) to write own programs based on LUA programming language. |
Data storage | WCCLite provides an archive of all data on non-volatile flash for events, measurements, counter values, and security events. |
Time management | WCCLite provides a multilevel time management solution CPU supports NTP, IEC 60870, and DNP3 time sync multi-sourcing and IOMOD devices have a time sync option with IEC 60870 protocol firmware. |
Time sync sources | Multi-time sync options (priority based): – Internal RTC clock with battery-based memory up to >15 years of lifetime; – NTP (Network Time Protocol) over TCP/IP; – IEC 60870-5 time sync support; – DNP3 time sync support; – IEC 61850 time sync support. |
Time sync precision | The time base operates with a time resolution of 1 ms. |
Communication interfaces | Interfaces for communication with IEDs, Meters, inverters, SCADA systems etc. |
Independent Ethernet ports | 2x 10/100 Mbps 10/100Base-T compliance IEEE 802.3, IEEE 802.3u standards, supports auto MDI/MDIX |
Serial ports | 2x RS485 (Standard ANSI/TIA/EIA-485-A) |
Serial ports | 1x RS232 (Standard EIA/TIA-232-E) Switchable with RS485 port1 |
Mobile communication | Available only with integrated WCCLite version with mobile communication module |
Mobile technology support | 4G (LTE) – Cat 4 up to 150 Mbps, 3G – Up to 42 Mbps, 2G – Up to 236.8 kbps |
Dual SIM card support | 2 SIM cards, auto-switch cases: weak signal, data limit, no network, network denied, data connection fail |
Other mobile info | Signal strength (RSSI), SINR, RSRP, RSRQ, RSCP, IMSI, ICCID, Signal strength LED indicators, SMS receive/send, APN management. |
LED indication | To indicate traffic on the interface every interface has an independent LED indication on the receive/send packet. |
Supported protocols | Host and sub-device communication protocols |
IEC 60870 | IEC 60870-5-101 Master support IEC 60870-5-101 Slave support IEC 60870-5-103 Master supportIEC 60870-5-104 Master support IEC 60870-5-104 Slave support (KEMA Cert.) + IEC 62351 (parts -3) security standard is supported by TLS encryption |
DNP3 | DNP3.0 TCP(LAN/WAN) Master support DNP3.0 TCP(LAN/WAN) Slave support DNP3.0 Serial Master support DNP3.0 Serial Slave support IEC 62351 (parts 3) security standard is supported by TLS encryption |
Modbus | Modbus RTU Master support Modbus RTU Slave support Modbus ASCII Master support Modbus ASCII Slave support Modbus TCP Master support Modbus TCP Slave support |
IEC 61850-8-1 | Client (Master) support of Editions 1, 2, 2.1 – MMS client – Read services – Write services – Static data sets – Report Control blocks – Controls – Discovery Server (Slave) support of Editions 1, 2, 2.1 – MMS server – Read services – Write services – Static data sets – Report Control blocks – Controls – Discovery IEC 62351 (parts -3, -4, -5, and -6) security standard is supported for authentication and TLS encryption |
Meter protocols | M-bus Master support DLMS/COSEM master support IEC 62056-21 master support IEC 62056-31 master support |
Other protocols | MQTT, RESTful API |
Cyber security | Comply with BDEW white paper, IEC 62351, and general cyber security practices |
Secure access | Secure access to all services (HTTPS, SSH) |
RBAC | Role-based access protection with login and password IEC 62351 by security standards is supported. |
User administration | Local user’s administration with different access levels Central user administration via RADIUS |
Password complexity | Fully customizable password policy: – minimum password length, – maximum password lifetime, – usage of lowercase characters, – upper case characters, – numeric, – special characters. |
Certificate storage | Internal Crypto Store for certificate management Import of certificates |
Power supply | |
Auxiliary power supply | 9-33VDC (full range) |
Insulation voltage | 3 kV |
Operating conditions | |
Operating temperature | -40°C … 85°C |
Storage temperature | -40°C … 85°C |
Relative humidity | max. 95 % (non condensing) |
Protection class | IP20 |
Dimensions | |
Installation type | DIN Rail mounting |
Case height x width x depth | 119 x 22.5 x 101 mm |